Facilities Energy Audit Status

The following summarizes the findings of an energy efficiency study conducted in 2002 for the City of Burlingame under the California Energy Commission's Energy Partnership Program. This study reviews the City's major energy using systems (these facilities are listed below). After review of the historical energy use, potential projects were determined and analyzed based on cost effectiveness.

This program provides technical assistance through energy audits, analyses, and low interest loans to California City and County governments in order to identify, install, and finance energy efficiency projects. The goal of the program is to reduce energy costs through the implementation of energy reduction measures in existing systems.

Facility Background and Site Information

The facilities audited have a combined building area of 136,825 square ft. with each facility's area as shown below:

 

Facility Area (sq. ft.)
City Hall

26,000

Library

48,000

Police Station

13,500

Fire Station #34

12,303

Fire Station #35

5,616

Fire Station #36

8,906

Golf Center

1,500

Recreation Center

21,000

Driving Range

NA

Total Building Area

136,825

 

Recommended Energy Projects

 

Facility

Project Description

Annual Cost
Savings ($)

Project Cost
Estimate ($)

Projected
Completion Date

City Hall

Convert LED Exit Signs in place of PL lamp based EXIT signs

[1] 

[1]

2003

City Hall

Replace old chiller and boiler at City with new water colled chiller and a new high efficiency boiler

$2,593

$90,865

2009-10

City Hall

Convert City Hall HVAC system controls from Pneumatic to Direct Digital Control

$3,998

$71,830

2012-13

City Hall

Convert City Hall Constant Volume  Reheat Air Handlers to VAV Reheat Systems

$7,180

$84,710

2016-17

City Hall

Provide a 1-KW Grid, grid connected PV System for City Hall

$2,276

$55,000

not budgeted

F.S. 35

Convert incandescent fixtures in equipment room to fixtures with T8 lamps and electronic ballasts

[1]

[1]

2003-04

F.S. 35

Replace Fire Station 35 Furnaces with new, high efficiency condensing furnaces

$351

$4,384

2010-11

F.S. 36

Convert incandescent fixtures with T8 lamps and electronic ballasts in apparatus room   

[1]

[1]

2004-05

Golf Center

Convert down lights from incandescent to PL 13 compact fluorescent lamps in Pro Shop

[1]

[1]

2002-03

Golf Center

Relocate Lighting Control Panel in golf Center to allow convenience switching of Drive Range and Putting range Metal Halide Lights when they are not in use

$748

$2,885

not budgeted

Library

Convert table & standing lamps on main & lower levels from incandescent to PL 13 compact fluorescent lamps

[1]

[1]

2002-03

Library

Provide stack area lighting controls for the new Library building

$2,329

$11,066

not budgeted

Library

Reduce excess emergency lighting level in library nigh light/emergency fixtures using District staff

$1,051

$700

2002-03

Police Station

Convert LED Exit Signs in place of PL lmap based EXIT signs

[1]

[1]

2004-05

Police Station

Retrofit fluorescent fixtures in the Police Station to StarCoat T8 lamps and low ballast factor electronic ballasts

$2,790

$14,479

2007-08

Police Station

Convert Police Station VAV System with inlet vanes to a VAV system using Variable Frequency Drives

$2,226

$23,848

2009-10

Police Station

Convert Police Station HVAC system controls from Pneumatic to Direct Digital Control

$5,015

$53,759

2012-13

Rec Center

Switch Electricity Account from Rate A-1 to Rate A-10

$3,680

$0

2002-03

Rec Center

Convert incandescent fixtures to compact fluorescent lamps; Convert fixtures to T8 lamps and electronic ballasts; provide LED Exit Signs

[1]

[1]

2002-03

Rec Center

Replace old condensing units of Recreation Center with new high efficiency condensing units

$2,239

$37,045

2008-09

Rec Center

Replace old hot water heating boiler in the Recreation Center with a new higher efficiency boiler

$1,072

$19,208

2010-11

[1]

Projected as one total project

$1,412

$9,362

 
  Totals

$38,962

$479,141